  • SNA-360-C2
  • Smoke and Heat Detector, EN Approvals                                                                           

    SNA-360-C2 analogue addressable photoelectric smoke/heat detectors are microprocessor controlled state-of-the-art detectors compatible with popular control and indicating equipment loop protocols. Up to 125 detectors can be connected to each alarm zone loop.

    Advanced electronics in conjunction with a photoelectric smoke sensing chamber and an electronic thermistor provide early detection of fire and high immunity against unwanted alarms. The heat sensor provides sensitive rate-of-rise operation or fixed-temperature operation when the response threshold value is exceeded.

    The SNA-360-C2 analogue addressable detector range provides fire detection and alarm system designers with a premium smoke/heat detector for life safety and property protection applications.


    • Features
    • Specifications
    • Approvals
    • Ordering Info
  • · Dual photoelectric smoke and heat sensors to detect either smoke, heat or a combination of the phenomena

    · Ideal for both fast-flaming and slow smouldering fires

    · Advanced algorithms provide analogue detection discrimination

    · Surface-mount device (SMD) circuit board design

    · High immunity against unwanted alarms

    · Stable smoke sensing chamber. No adjustment or replacement required

    · Durable heat sensor. No adjustment or replacement required

    · Sleek low-profile housing 

    · Dual LEDs for 360° visibility

    · Convenient 2-wire connection to many popular loop protocols

    · Easy installation with simple address setting DIP switches

    · Available with 125 usable detector address settings per loop when connected  to Numens control and indicating equipment

    · Low maintenance


  • SNA-360-C2

    Operating voltage

    DC (17 ~ 28) V

    Start-up current

    ≤ 400 µA

    Start-up time

    ≤ 30 s

    Quiescent current

    ≤ 260 µA

    Sampling time

    ≤ 2 s

    Alarm response threshold (smoke)

    (0.08 ~ 0.15) dB/m

    Alarm response threshold (heat)

    59 °C static, and rate-of-rise a

    Alarm current (max)

    2 mA

    Alarm indicator

    Dual red LEDs

    Reset voltage

    ≤ 3 V

    Reset time

    ≤ 30 s

    Usable addresses per alarm loop

    125

    Operating temperature

    (-10 ~ +55) °C

    Operating humidity

    (0 ~ 95) % RH, non-condensing

    Storage temperature

    (-25 ~ +80) °C

    Storage humidity

    (0 ~ 98) % RH, non-condensing

    Dimensions (excluding contacts)

    Φ 102 mm × 45 mm

    Ingress protection rating

    IP-42

    aDetectors are factory-configured for 30 k/min and comply with EN 54-5 class A1 and class A2.