•   Contact Us
  • T : +86 574 8281 7218
    F : +86 574 8300 1379
  • 46-2 MoGao Road
    Dong Qian Lake
    Ningbo,Zhejiang
    China 315121
  • Home > Products
  • HNA-360-HL
  • Heat Detector, Remote LED Output, EN54 Approvals                                                                                                                                                      

    HNA-360-HL analogue addressable heat detectors are microprocessor controlled state-of-the-art detectors compatible with popular control and indicating equipment loop protocols. Up to 125 detectors can be connected to each alarm zone loop.

    An electronic thermistor sensor provides sensitive rate-of-rise alarm operation, or fixed-temperature operation when the response threshold value is exceeded. 

    The HNA-360-HL analogue addressable detectors range provides fire detection and alarm system designers with a premium heat detector for property protection applications where smoke or multi-sensor detectors may not suitable due to environmental conditions.


    • Features
    • Specifications
    • Approvals
    • Ordering Info
  • · Advanced algorithms provide analogue detection discrimination

    · Surface-mount device (SMD) circuit board design

    · Durable sensor. No adjustment or replacement required

    · Sleek low-profile housing design

    · Dual LEDs for 360° visibility

    · Convenient 2-wire connection to many popular loop protocols

    · Easy installation with simple address setting DIP switches

    · Available with 125 usable detector address settings per loop when connected to Numens control and indicating equipment

    · Optional remote LED output

    · Low maintenance


  • HNA-360-HL

    Operating voltage

    DC (17 ~ 28) V

    Start-up current

    ≤ 400 µA

    Start-up time

    ≤ 30 s

    Quiescent current

    ≤ 260 µA

    Alarm current (max)

    5 mA

    Sampling time

    ≤ 2 s

    Alarm response threshold

    59 °C static, and rate-of-rise a

    Alarm indicator

    Dual red LEDs

    Remote LED output current (max)

    2 mA

    Reset voltage

    ≤ 3 V

    Reset time

    ≤ 30 s

    Usable addresses per alarm loop

    125

    Operating temperature

    (-10 ~ +55) °C

    Operating humidity

    (0 ~ 95) % RH, non-condensing

    Storage temperature

    (-25 ~ +80) °C

    Storage humidity

    (0 ~ 98) % RH, non-condensing

    Dimensions (excluding contacts)

    Φ 102 mm × 45 mm

    Ingress protection rating

    IP-42

    aDetectors are factory-configured for 30 k/min and comply with EN 54-5 class A1 and class A2.



  • EN54-5

    Kitemark 

    HNA-360-HL

    ü

    ü


  • 2-Wire

    Remote Indicator

    Base

    Package

    HNA-360-HL

    ü

    ü

    CN304A 

    100Pcs/Carton