  • 6001-02
  • Control Panel, 2-loop                                                                                                                                                                                            

    The 6001-02 analogue addressable control and indicating equipment forms the central part of a fire detection and alarm system. The fully networkable 6001-02 is compatible with Numens addressable devices and can also be connected to non-addressable devices when used with addressable input modules.

    Default configuration programming facilitates out-of-box installation and rapid commissioning. A powerful and versatile cause-and-effect PC-based programming tool enables rapid customization with software for sites that require special operating features.

    The 6001-02 comes standard with features that allows flexibility and expandability.

    The 6001-02 control panel provides fire detection and alarm system designers with a premium product for life safety and property protection applications.



    • Features
    • Specifications
    • Approvals
    • Ordering Info
  • · 2 loop detection circuits

    · Networkable, up to 4 control panels

    · Supports up to 125 addressable devices per loop

    · Automatic device detection on start-up

    · Automatic device type-code verification

    · 2 independently programmable non-addressable sounder output circuits

    · 2 programmable relay outputs

    · Fault relay output

    · Remote disable and evacuation inputs

    · Backlit LCD display providing 4 rows of 40 characters

    · 16 zone fire alarm LED indicators

    · 3000 event history log

    · Attractive designer enclosure available in white

    · Recessed mounting

    · Easy installation


  • 6001-02

    Operating voltage

    AC (85 ~ 260) V / 50/60 Hz

    Mains supply current limit

    1.5 A @ AC 230 V

    Mains supply fuse

    4 A / AC 250 V slow blow (20 mm)

    Mains supply fault threshold voltage

    ≤ AC 60 V

    Power supply

    2.2 A @ DC 28 V

    Standby battery capacity (2 × DC 12 V)

    7.2 Ah

    Maximum battery current draw

    1.5 A @ maximum operating temperature

    Battery fuse

    6 A resettable (electronic fuse)

    Battery fault threshold voltage

    < DC 20 V

    Quiescent current

    110 mA @ 28.5 V

    Addressable loops

    2

    Number of connected devices per loop

    125

    Loop current (max)

    400 mA

    Loop monitoring

    Open- and short-circuit

    Configurableaudio/visual alarm groups (max)

    512

    Non-addressable audio/visual alarm device driver

    800 mA

    Non-addressable audio/visual alarm end-of-line resistor

    10 kΩ

    Alarm zone monitoring

    Open- and short-circuit

    Alarm zone voltage (max)

    DC 27.5 V

    Alarm zone fuse

    1.1 A resettable (electronic fuse)

    Number of programmable output relays

    2

    Ancillary fire C/O relay

    2 x (1.0 A @ DC 30 V / 1 A @ AC 240 V)

    Ancillary fault N/C relay

    1.0 A @ DC 30 V / 1 A @ AC 240 V

    Auxiliary supply

    DC 28 V @ 300 mA

    Evacuation start / stop input

    Non-latching, voltage-free

    Remote reset input

    Non-latching, voltage-free

    Number of networked panels

    4

    Terminal wiring

    (0.4 ~ 2.5) mm2

    Operating temperature

    (-5 ~ +40) °C

    Operating humidity

    (0 ~ 95) % RH, non-condensing

    Storage temperature

    (-25 ~ +80) °C

    Storage humidity

    (0 ~ 98) % RH, non-condensing

    Dimensions (h × w × d)

    (420 × 337 × 99) mm

    Weight (excluding batteries)

    4.0 kg

    Requires 6001-06 loop expansion card.



  • CE

    6001-02

    ü



  • 2 Loop Detection Circuits

    Package

    6001-02

    ü

    6Pcs/Carton