  • 4001-03
  • Control Panel, 8-zone                                                                                                     

    The 4001-03 non-addressable control and indicating equipment forms the central part of a fire detection and alarm system. The 4001-03 is compatible with Numens non-addressable devices.

    The 4001-03 comes standard with features that allows flexibility and expandability. Default configuration programming facilitates out-of-box installation and rapid commissioning. 

    The 4001-03 control panel provides fire detection and alarm system designers with an economical product for life safety and property protection applications.

                                                  

    • Features
    • Specifications
    • Approvals
    • Ordering Info
  • · 8 detection zones

    · Supports up to 32 non-addressable devices per alarm zone circuit

    · Configurable non-latching alarm zones

    · Configurable alarm dependency (zone coincidence detection)

    · Configurable timer to delay output activation (up to 10 min)

    · Capacitor end-of-line device.

    · 3 Access Levels

    · Single-person test mode

    · Day/night mode configurable

    · Manual activation of alarm devices

    · Supervised auxiliary DC 24 V output

    · 2 programmable non-addressable alarm output circuits

    · 2 unmonitored relay contacts for Fire Alarm Condition outputs

    · 1 unmonitored relay contact for Fault Condition output

    · 3 voltage-free inputs for remote reset, evacuation start/stop, and Day/Night mode

    · Clear alarm zone LED indicators, with a single indicator for Fault, Disable and Test Condition indication

    · Recessed mounting enclosure

    · Supports up to 7 Repeater Panels

    · Easy installation


  • 4001-03

    Operating voltage

    AC (85 ~ 260) V / 50/60 Hz

    Mains supply current limit

    720 mA @ AC 230 V

    Mains supply fuse

    4 A / AC 250 V slow blow (20 mm)

    Mains supply fault threshold voltage

    ≤ AC 60 V

    Power supply

    2.2 A @ DC 28.5 V

    Standby battery maximum capacity (2 × DC 12 V)

    7.2 Ah

    Maximum battery current draw

    1.5 A @ maximum operating temperature

    Battery fuse

    6 A resettable (electronic fuse)

    Battery fault threshold voltage

    < DC 20 V

    Quiescent current

    30 m A @ DC 28 V

    Detection zone circuits

    8

    Number of connected devices per detection zone circuit

    32

    Detector zone quiescent current

    5 mA

    Detector zone alarm current

    160 mA

    Detector zone wiring characteristics (max)

    40 Ω / 0.47 µF

    Detection zone end-of-line capacitor

    22 µF / DC 50 V

    Manual call point resistor value

    (470 ~ 689) Ω

    Alarm zone outputs

    2

    Alarm zone current

    910 mA

    Alarm zone end-of-line resistor

    (20 ~ 40) kΩ

    Alarm zone monitoring

    Open- and short-circuit

    Alarm zone voltage (max)

    DC 27.5 V

    Alarm zone fuse

    1.1 A resettable (electronic fuse)

    Number of programmable output relays

    2

    Ancillary fire C/O relay

    2 × (1.0 A @ DC 30 V / 1 A @ AC 240 V)

    Ancillary fault N/C relay

    1.0 A @ DC 30 V / 1 A @ AC 240 V

    Auxiliary supply

    DC 28 V @ 300 mA

    Evacuation start / stop

    Non-latching, voltage-free

    Day / Night mode

    Non-latching, voltage-free

    Remote reset

    Non-latching, voltage-free

    Terminal wiring

    (0.4 ~ 2.5) mm2

    Operating temperature

    (0 ~ +50) °C

    Operating humidity

    (0 ~ 95) % RH, non-condensing

    Storage temperature

    (-25 ~ +80) °C

    Storage humidity

    (0 ~ 98) % RH, non-condensing

    Dimensions (h × w × d)

    (402 × 337 × 99) mm

    Weight (excluding batteries)

    4.0 kg



  • CE

    4001-03

    ü



  • 8 Detection Zone Circuits

    Package

    4001-03

    ü

    6Pcs/Carton