•   Contact Us
  • T : +86 574 8281 7218
    F : +86 574 8300 1379
  • 46-2 MoGao Road
    Dong Qian Lake
    Ningbo,Zhejiang
    China 315121
  • Home > Products
  • 6004-01
  • Control Panel, 1-loop, Metal Enclosure                                                                                                                          

     

    The 6004 analogue addressable control and indicating equipment forms the central part of a fire detection and alarm system. The fully networkable 2-wire 6004 is compatible with Numens addressable devices and can also be connected to non-addressable devices when used with addressable input modules.

    Default configuration programming facilitates out-of-box installation and rapid commissioning. A powerful and versatile cause-and-effect PC-based programming tool enables rapid customization with software for sites that require special operating features.

    The 6004 comes standard with features that allows flexibility and expandability.

    The 6004 control panel provides fire detection and alarm system designers with a premium product for life safety and property protection applications.

                                                      

    • Features
    • Specifications
    • Approvals
    • Ordering Info
  •   • Single loop or 2-loop options available
      • Single loop, expandable to 2-loops available
      • Networkable, up to 4 control panels
      • Supports up to 125 addressable devices per loop
      • Automatic device detection on start-up
      • Automatic device type-code verification
      • 2 independently programmable non-addressable sounder output circuits
      • 2 programmable relay outputs
      • Fault relay output
      • Remote disable and evacuation inputs
      • Backlit LCD display providing 4 rows of 40 characters
      • 16 zone fire alarm LED indicators
      • 3000 event history log
      • Attractive designer enclosure available in white
      • Surface mounting
      • Rugged metal enclosure
      • Easy installation
                                    

  • 6004-01

    Operating voltage

    AC (85 ~ 260) V /  50/60 Hz

    Mains supply current limit

    1.5 A @ AC 230 V

    Mains supply fuse

    4 A / AC 250 V slow blow (20 mm)

    Mains supply fault  threshold voltage

    ≤ AC 60 V

    Power supply

    2.2 A @ DC 28 V

    Standby battery capacity (2 × DC 12 V)

    7.2 Ah

    Maximum battery current  draw

    1.5 A @ maximum operating temperature

    Battery fuse

    6 A resettable (electronic fuse)

    Battery fault threshold  voltage

    < DC 20 V

    Quiescent current

    100 mA @ 28.5 V

    Addressable loops

    1

    Number of connected devices per loop

    125

    Loop current (max)

    400 mA

    Loop monitoring

    Open- and short-circuit

    Configurableaudio/visual alarm groups (max)

    512

    Non-addressable audio/visual alarm device driver

    800 mA

    Non-addressable audio/visual alarm end-of-line resistor

    10 kΩ

    Alarm zone monitoring

    Open- and short-circuit

    Alarm zone voltage (max)

    DC 27.5 V

    Alarm zone fuse

    1.1 A resettable (electronic fuse)

    Number of programmable output relays

    2

    Ancillary fire C/O relay

    2 x (1.0 A @  DC 30 V / 1 A @ AC 240 V)

    Ancillary fault N/C relay

    1.0 A @ DC 30 V / 1 A @ AC 240 V

    Auxiliary supply

    DC 28 V @ 300 mA

    Evacuation start / stop input

    Non-latching, voltage-free

    Remote reset input

    Non-latching, voltage-free

    Number of networked panels

    4

    Terminal wiring

    (0.4 ~ 2.5) mm2

    Operating temperature

    (-5 ~ +40) °C

    Operating humidity

    (0 ~ 95) % RH,  non-condensing

    Storage temperature

    (-25 ~ +80) °C

    Storage humidity

    (0 ~ 98) % RH,  non-condensing

    Dimensions (h × w × d)

    (420 × 337 × 99) mm

    Weight (excluding batteries)

    4.0 kg

     

  • EN 54-2 a

    EN 54-4 b

    6004-01

    ü

    ü

    a EN 54-2 Control  and indicating equipment

    bEN 54-4 Power  supply equipment

     

  •  

    1 Loop Detection Circuit

    Package

    6004-01

    ü

    6Pcs/Carton