•   Contact Us
  • T : +86 574 8281 7218
    F : +86 574 8300 1379
  • 46-2 MoGao Road
    Dong Qian Lake
    Ningbo,Zhejiang
    China 315121
  • Home > Products
  • 6002-01
  • Control Panel, 24-loop muximum                                                                                  

    The 6002 analogue addressable control andindicating equipment forms the central part of a fire detection and alarmsystem. The 6002 is compatible with Numens addressable devices and supportsboth Numens ST and TP loop protocols. Either 125 or 250 devices per loop aresupported. Non-addressable devices can also be connected to the 6002, when used with addressable input modules.

    The 6002 comes standard with 2-loops, and is expandable up to 24-loops.

    Default configuration programming facilitates out-of-box installation and rapid commissioning. A powerful and versatile cause-and-effect PC-based programming tool enables rapid customization with software for sites that require special operating features.

    The 6002 control panel provides fire detection and alarm system designers with a premium product for life safety and propertyprotection applications.



    • Features
    • Specifications
    • Approvals
    • Ordering Info
  •      · Two addressable loops, internally expandable to 4 or 6-loops

         · Six-loop expansion panel provides a maximum system size of 24-loops

         ·  Supports up to 64 repeater panels

         ·  Supports 125 or 250 addressable devices per loop

         ·  Supports both Numens ST and TP loop protocols

         ·  Automatic device detection on start-up

         ·  Automatic device type-code verification

         ·  2 independently programmable non-addressable sounder output circuits

         ·  2 programmable relay outputs

         ·  Fault relay output

         ·  Remote disable and evacuation inputs

         ·  Backlit LCD display providing 4 rows of 40 characters

         · 32, 64, 96, or 128 zone fire alarm LED indicators

         · 3000 event history log

         ·  Attractive designer enclosure available in white

         ·  Surface mounting

         ·  Easy installation


  •                                                                                   6002-01

    Operating voltage

    AC (100 ~ 260) V /  50/60 Hz

    Mains supply fuse

    4 A / AC 250 V slow blow (20 mm)

    Mains supply fault  threshold voltage

    ≤ AC 60 V

    Power supply

    4.3 A @ DC 28.5 V

    Standby battery capacity (2 × DC 12 V)

    7.2 Ah

    Maximum battery current  draw @ maximum operating temperature

    1.5 A

    Battery fuse

    10 A resettable (electronic fuse)

    Battery fault threshold  voltage

    < DC 20 V

    Quiescent current

    200 mA @ 28.5 V

    Addressable loops

    2, expandable to 4a, 6a  12b, 18b or 24b

    Number of connected devices per loop

    125 (ST protocol)/250 (TP protocol)

    Loop current (max)

    400 mA

    Loop monitoring

    Open- and short-circuit

    Configurable audio/visual alarm groups (max)

    512

    Non-addressable audio/visual alarm device driver

    800 mA

    Non-addressable audio/visual alarm end-of-line resistor

    10 kΩ

    Alarm zone monitoring

    Open- and short-circuit

    Alarm zone voltage (max)

    DC 27.5 V

    Alarm zone fuse

    1.1 A resettable (electronic fuse)

    Number of programmable output relays

    2

    Ancillary fire C/O relay

    2 x (1.0 A @  DC 30 V / 1 A @ AC 240 V)

    Ancillary fault N/C relay

    1.0 A @ DC 30 V / 1 A @ AC 240 V

    Auxiliary supply

    DC 28 V @ 300 mA

    Evacuation start / stop input

    Non-latching, voltage-free

    Remote selected disablement input

    Non-latching, voltage-free

    Number of networked repeaters

    64

    Terminal wiring

    (0.4 ~ 2.5) mm2

    Operating temperature

    (-5 ~ +40) °C

    Operating humidity

    (0 ~ 95) % RH,  non-condensing

    Storage temperature

    (-25 ~ +80) °C

    Storage humidity

    (0 ~ 98) % RH,  non-condensing

    Dimensions (h × w × d)

    (485 × 465 × 155) mm

    Weight (excluding batteries)

    10.0 kg

    a Requires 6002-02 loop expansion card.

    b Requires 6002-03 network loop expansion panel.

     

     

  •  

    EN 54-2 b

    EN 54-4 c

    6002-01

    ü

    ü

    a Third-party conformance assessment has not been  undertaken.

    b EN 54-2 Control  and indicating equipment

    cEN 54-4 Power  supply equipment

     

  • 2 Loop Detection Circuit

    Package

    6002-01

    ü

    1Pcs/Carton